Denggao Electric Co., Ltd.
Zhejiang, China
Diamond Member Since 2019
Audited Supplier
Manufacturer/Factory & Trading Company
Sample Available
OEM/ODM Service
Factory Tour
33kv 630A High Quality Polymer Load Break Isolate Switch
Reference FOB Price: | US $100.00-1,500.00 / Piece |
---|---|
Min. Order: | 1 Piece |
Type: | High-voltage |
---|---|
Structure: | Three-column Disconnector |
Installation: | Outdoor High-voltage |
Operation: | Electric |
Grounding Mode: | Grounding |
Movement Mode: | Horizontal Rotary Type |
Basic Info
Model NO.
GW9
Number of Poles
Three Pole
Structure of Operating
Electric
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
853530900
Production Capacity
10000PCS/Yea
Product Description
General
The "(H)GW9-12" outdoor high voltage switch equipment of single phase AC 50Hz.The product is suitable for power systems with a rated voltage of 10kV to make or break power supply under circumstances of voltage and no load. The isolator adopts an isolated hook rod to operate.
Service conditions
1. The altitude does not exceed 1000m.
2. The ambient air temperature: Maximum:+40ºC; Minimum:-30ºC, Paramos:-40ºC
3. The wind pressure does not exceed 700Pa. (corresponding to 34m/s wind speed).
4. The earthquake intensity does not exceed 8 degrees.
5. The working situation hasn't frequent violent vibration.
6. The installation site of an ordinary type isolator should be kept away from gas, smoke chemical deposition,salt-spray fog, dust, and other explosive and corrosive matters that affect seriously the insulation and conduction capability of the isolator.
7. Pollution-proof type isolator is applied to severe filthy conduction area; however, it shouldn't be any explosive matters and matters causing a fire.
The "(H)GW9-12" outdoor high voltage switch equipment of single phase AC 50Hz.The product is suitable for power systems with a rated voltage of 10kV to make or break power supply under circumstances of voltage and no load. The isolator adopts an isolated hook rod to operate.
Service conditions
1. The altitude does not exceed 1000m.
2. The ambient air temperature: Maximum:+40ºC; Minimum:-30ºC, Paramos:-40ºC
3. The wind pressure does not exceed 700Pa. (corresponding to 34m/s wind speed).
4. The earthquake intensity does not exceed 8 degrees.
5. The working situation hasn't frequent violent vibration.
6. The installation site of an ordinary type isolator should be kept away from gas, smoke chemical deposition,salt-spray fog, dust, and other explosive and corrosive matters that affect seriously the insulation and conduction capability of the isolator.
7. Pollution-proof type isolator is applied to severe filthy conduction area; however, it shouldn't be any explosive matters and matters causing a fire.
Technical parameters | ||||
No. | Item | Unit | Data | |
1 | Rated frequency | Hz | 50 | |
2 | Rated voltage | kV | 12 | |
3 | Rated current | A | 630(1250) | |
4 | Rated short-time withstand current and duration | kA/s | 20(25)/4 | |
5 | Rated peak withstand current | kA | 50(63) | |
6 | Rated short-time power frequency withstand voltage | Interphase, to earth(dry) | kV/min | 42/1 |
Interphase, to earth(wet) | 30/1 | |||
Break(dry) | 48/1 | |||
Break(wet) | 36/1 | |||
7 | Rated lightning impulse withstand voltage | Interphase, to earth | kV | 75 |
Break | 85 | |||
8 | Circuit resistance | μΩ | ≤80 | |
9 | Mechanical life | Times | 3000 | |
10 | Pollution grade | e class | ||
11 | Creepage distance | mm | ≥372 | |
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate. |