1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv

Product Details
Customization: Available
Certification: CCC, ISO9001
Voltage Level: Medium Voltage
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Patents Awarded
The supplier had awarded 4 patents, you can check the Audit Report for more information
Management Certification
The supplier has quality management system certification, including:
ISO9001:2015 certificate
ISO45001:2018 certificate
ISO14001
Product Certification
The supplier's products already have relevant certification qualifications, including:
KEMA
to see all verified strength labels (33)
  • 1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv
  • 1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv
  • 1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv
  • 1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv
  • 1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv
  • 1250kVA 15/0.4kv Compact Cubicle Transformer Substation at Rated Voltage 11kv 13.8kv 15kv
Find Similar Products

Basic Info.

Model NO.
YB
Structure
Box Transformer
Altitude
Less Than1000m
Rated Frequency
50/60Hz
Transfer Current
1200-3150A
Rated Current
400,630,1250A
Transport Package
Nude
Trademark
DGG
Origin
China
HS Code
853720900
Production Capacity
100sets/Year

Product Description

Photos of Product

Electrical power transmission and distribution experts in china

This substation has 3 main compartments:  
There are the Transformer Compartments,
High/Medium Voltage Switchgear compartment and
Low Voltage Switchgear compartment.HV & LV compartments are with completed function.

1. High Voltage compartment has various power supply methods when testing power supply at 1 time, it also can be installed with High Voltage testing appliances to reach the demand of High Voltage testing.  

2. The transformer compartment can use S7, S9, S11, or other low-loss oil-immersed transformers, or dry transformers.  The transformer compartment has automatic start wind cooling systems and lighting systems.

3. Low Voltage compartment can be made according to users' need, it adopts fixed or assembled structure to be electrical power supply system, it has many functions like light distribution, power distribution, reactive power, electrical power testing..etc to improve the power distribution quality and satisfy the user.

This substation is a very important power distribution and supply unit in the electrical cable power net. It is a kind of completed set of power supply with H.V.controlling, protection, and converting distribution.. it is used in 3 phase AC 50Hz and rated current max 1600KVA transformer. It is widely used in industrial and mining enterprises, residential quarters, hospitals, malls, high-rise buildings, and other distribution systems.

For this substation, we mainly produce & export 11KV, 15KV,20KV,24KV, and 33KV types.

For customized special type, once we get clear technical data or single line diagram(SLD), we also can make it.

Ambient Environment

1. Ambient temperature: -25ºC~+40ºC
2. Altitude: less than1000m
3. Relative humidity
Daily average less than 95% Average value of water vapor pressure less than 2.2kpa
Monthly average less than 90% Average value of water vapor pressure less than 1.8kpa
4. Seismic intensity: less than magnitude 8
5. Outside wind speed less than 35m/s
6. Apply to the places that have no fire, no explosion danger, and no chemical corrosion 

Technical Data

High Voltage Unit

Item

Unit

Parameter

Rated frequency

Hz

50/60

Rated Voltage

kV

6.6

11

33

Max service voltage

kV

7.2

12

36

Rated current

A

400,630,1250

Transfer current

A

1200-3150

1min power frequency withstand voltage

to earth and phase

to phase /Fracture

kV

42/48,85/95

BIL: to earth and phase to phase /Fracture

kV

75/85,170/185

Rated short circuit breaking current

kA

25,31.5

Transformer

Unit

Rated Voltage

kV

6,11,33

Rated Capacity

kVA

30-2000

Tap ranging

%

+/-2x2.5%,+/-5%

Vector Group

 

Yyn0, Dyn11

Impedance

%

4,4.5,6,8

Low Voltage Unit

Rated Voltage

V

220,380,690,800

The main circuit rated current

A

50-4000

Branch current

A

5-800

Enclosure

Protection Level

 

HV Room:IP33

Transformer Room: IP23

LV Room: IP33

 

Noise level

dB

≤50