Our factory
We are professional manufacturer of current transformer ,voltage transformer, Vacuum Circuit Breakers/Recloser,Isolation switches,Dropout Fuse Cut-out,Lightning Arresters,High and Low Voltage Cabinets,Metering Devices,Power Distribution Transformers etc.
General
ZW20-12F series outdoor high-voltage AC boundary vacuum circuit breaker (hereinafter referred to as "Boundary circuit breaker") is an outdoor high-voltage switchgear with three-phase AC 50Hz and a rated voltage of 12kV. It is mainly composed of a vacuum circuit breaker body, distribution automation feeder terminal, voltage transformer, control cable, etc. the circuit breaker body is equipped with a vacuum arc extinguishing chamber, current transformer, zero sequence current transformer, and other components.
Boundary circuit breakers have remote management mode, and the protection control function and communication function can be reliably judged, and the detection is used in substations, industrial and mining enterprises, and urban and rural power grids for control and protection. It is especially suitable for places requiring frequent operation and urban milliampere zero sequence current and phase-to-phase fault short-circuit current, so as to realize automatic removal of single-phase grounding fault and phase-to-phase short-circuit fault.
Boundary circuit breakers adopt vacuum arc extinguishing chamber and SF6 gas insulation. The box adopts foreign advanced gas sealing, explosion-proof, and insulation structure technology, with excellent overall sealing performance. Its spring operating mechanism adopts a miniaturized design, and excellent performance and action reliability are much higher than the domestic traditional spring operating mechanism.
The boundary circuit breaker shall comply with GB / T 1984-2014 high voltage current circuit breaker, DL / T 402 - 2016 high voltage current circuit breaker, DL / T 403 - 2000 technical conditions for ordering 12kV - 40.5kV high voltage vacuum circuit breaker, DL / T 721 - 2013 remote terminal of distribution automation system and other technical standards.
Model Description
Main Advantages
1. Matching with smart grid: It can realize three-stage protection, zero-sequence grounding protection, reclosing and remote communication functions.
2. Flexible and convenient operation: it can store electric energy, open and close electrically, or store energy manually, open and close manually, and can operate at close range.
3. Low operating power and high reliability: The operating power (about 30W) of the newly designed miniaturized spring operating mechanism is reduced to the lowest level.
4. Reliable sealing performance: SF6 gas pressure is zero gauge pressure, and mature sealing structure technology is adopted, which has reliable sealing performance and is not easy to leak.
5. Unique way of entering and exiting: Uses silicone rubber sleeve, the insulation distance between the terminals is sufficient, and the external insulation performance is excellent.
6. Excellent safety performance: There is an explosion-proof device on the top of the box, even if there is an internal failure, there will be no leakage of high-temperature gas or splashes.
7. Flexible installation method: it can be installed on the pole or by sitting.
8. The rated current is large, up to 1250A, and the breaking capacity is strong, up to 25kA.
Main Technical Parameters
No. |
Item |
Unit |
Data |
1 |
Rated frequency |
Hz |
50 |
2 |
Rated voltage |
kV |
12 |
3 |
Rated current |
A |
630 |
1250 |
4 |
Rated short-time power frequency withstand voltage |
Interphase, to earth(wet) |
kV/min |
34/1 |
Interphase, to earth(dry) |
42/1 |
Fracture (dry) |
48/1 |
Secondary circuit to earth |
2/1 |
5 |
Rated lightning impulse withstand voltage |
Interphase, to earth |
kV |
75 |
Fracture |
|
85 |
6 |
Rated short-circuit breaking current |
kA |
20/25 |
7 |
Rated short-circuit making current(peak) |
|
50/63 |
8 |
Rated short-time withstand current and duration |
kA/s |
(20/25)/4 |
9 |
Rated peak withstand current |
kA |
50/63 |
10 |
Rated short-circuit breaking current breaking times |
Times |
30 (E2 Level) |
11 |
Gas Rated Gauge Pressure |
MPa |
0 |
12 |
Main circuit resistance |
μΩ |
≤120 |
13 |
Rated Operating Voltage and Rated Voltage for auxiliary(control) circuit |
V |
AC/DC220,DC48,DC24 |
14 |
Mechanical life |
Times |
10000 (M2 level) |
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate. |
Outline And Installation Dimension
Test Reports
All products have undergone professional testing and certification.
Our Customer
Our customers are located all over the world.