• Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
  • Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
  • Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
  • Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
  • Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
  • Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement

Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement

Application: Metering
Type: Current Transformer
Phase: Single
Operation Condition: Indoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
LXK
Insulating Medium
Epoxy Resin
Installation
Busbar Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year

Product Description

GENERAL

These series of transformers are used indoors. They are used for three phases of overdriven current protection in the electric not-useful-ground neutral system up to rated frequency 50Hz or 60Hz and rated voltage 35kV. The transformers are fitting with the relay too.

Being installed, at first, make the product dimidiation. Then make it coalition use bolt. Can be loaded in hot-line conditions.



MODEL AND MEANING
Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
NORMAL ENVIRONMENTAL CONDITIONS
  1. Altitude: Should not exceed 1000m
  2. Ambient temperature: -5ºC ~ +40ºC
  3. Air relative humidity: ≤85%
  4. Air relative site: Indoor.

TECHNICAL PARAMETERS
    1. Rated secondary current: 5A or 1A
    2. Power factor: cosφ=0.8(lag)
    3. Rated frequency: 50Hz or 60Hz
    4. Rated primary current, rated output, and accurate level see table 1
    5. Insulating property: primary winding to secondary winding and ground, and secondary winding to the ground can bear the power frequency withstand voltage 3kV for 1min.
    Table 1: Current Part of the Technical Parameters
     
    Rated primary current(A) Accuracy Class Rated Output (VA)
    60-75 10P5 2.5
    100 3.75
    150 2.5
    200-300 3.75
    400-600 5
    100 2.5
    150-200 10P10 2.5
    300-400 3.75
    500 5
    600 5
     
     
    Type of Relay Connecting Method of Relay Windings Relay Calibration Primary Zero Sequence Current
    LJK-Φ120
    LJK-Φ160
    Series 15x1 2-5
    30x1
    Parallel 15x2 3-8
    30x2
    LJK-Φ200 Series 15x1 3-6
    30x1
    Parallel 15x2 3-10
    30x2

     

    OUTLINE AND INSTALLATION DIMENSIONS
    Lxk - (80 ~120) Zero Sequence Electric Current Transformer Suitable for Power Measurement
    Model Number ΦD Φd H h a b c e
    LXK(KXLXK) - Φ80 165 80 175 82.5 120 104 120 56
    LXK(KXLXK) - Φ100 180 100 195 92.5
    LXK(KXLXK) - Φ120 204 120 215 102.5
    LXK(KXLXK) - Φ150 234 150 245 117.5
    LXK(KXLXK) - Φ180 263 180 275 132.5
    LXK(KXLXK) - Φ200 303 200 320 156
    LXK(KXLXK) - Φ240 347 240 385 185 160 120 142 80
     
     

    Send your message to this supplier

    *From:
    *To:
    *Message:

    Enter between 20 to 4,000 characters.

    This is not what you are looking for? Post a Sourcing Request Now

    You Might Also Like

    360° Virtual Tour

    Diamond Member Since 2019

    Suppliers with verified business licenses

    Manufacturer/Factory & Trading Company
    Number of Employees
    302
    Year of Establishment
    1996-09-15