• Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer
  • Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer
  • Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer
  • Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer
  • Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer
  • Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer

Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer

Application: Instrument, Metering
Type: Voltage Transformer
Phase: Single
Operation Condition: Indoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
LZZBW -10
Insulating Medium
Epoxy Resin
Installation
Extension Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year

Product Description

Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current TransformerGENERAL

This type of current transformer adopts epoxy-resin vacuum casting and a fully closed single-phase structure for indoor use, is applicable for power systems of rated frequency 50Hz or 60Hz and rated voltage up to and including 10kV, used for electric energy metering, current measurement, and relay protection.

It complies with the standards GB 20840.1 - 2010 Instrument transformers 
Part 1: General requirements, GB 20840.2 - 2014 Instrument transformers
Part 2: Additional requirements for current transformers, and JJG 313-2010 Instrument Current Transformers



MODEL AND MEANING

Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current TransformerLzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer
NORMAL USAGE CONDITIONS
  1. Altitude: should not exceed 1000m
  2. Ambient temperature: -5ºC ~ +40ºC
  3. Air relative site: Indoor.

TECHNICAL PARAMETERS
  1. Compliance Standards: GB/T 20840.1&3 and IEC61869-1&2
  2. Insulation level:12/42/75kV
  3. Power factor:cosφ=0.8(lag)
  4. Rated secondary current: 5A or 1A
  5. Rated frequency:50Hz or 60Hz
  6. Weight: 36kg

TECHNICAL RATIO

Table 1: Transformation Ratio Parameters
 
Rated Primary
Current (A)
Accuracy class Rated output(VA) Rated Short-Time Thermal Current(kA/S) Rated Insulation Level (kA)
5 0.2S/10P10
0.2S/0.5.10P10
0.2S/10P10/10P10
0.2S/10P20




 
10/15
10/10/15
10/15/15
10/15



 
0.36 0.9
10 0.72 1.8
15 1.08 2.7
20 1.44 3.6
25 1.8 4.5
30 2.16 5.4
40 2.88 6.3
50 3.6 7.2
60 4.32 8.1
75 5.4 13.5
80 5.76 14.4
100 7.2 18
120 8.64 21.6
150 10.8 27
200 14.4 36
250 18 45
300 21.6 54
400 28.8 63
500 36 90
600 43.2 108
800 57.6 120
1000 / 5 72 144


OUTLINE AND INSTALLATION DIMENSION
Lzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current TransformerLzzbw -10 Indoor / Single-Phase Fully Enclosed Post Type Current Transformer

Send your message to this supplier

*From:
*To:
*Message: