• Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer
  • Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer
  • Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer
  • Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer
  • Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer
  • Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer

Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer

Application: Instrument, Metering
Type: Voltage Transformer
Phase: Single
Operation Condition: Indoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
JDZ10 -10
Insulating Medium
Epoxy Resin
Installation
Extension Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year

Product Description

Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage TransformerJdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage TransformerGENERAL

This type of voltage transformer adopts epoxy-resin vacuum casting and a semi-enclosed single-phase structure for indoor use, is applicable for power systems of rated frequency 50Hz or 60Hz and rated voltage up to and including 10kV, used for electric energy metering and voltage measurement.

It complies with the standards GB 20840.1 - 2010 Instrument transformers 
Part 1: General requirements, GB 20840.3 - 2014 Instrument transformers
Part 2: Additional requirements for Voltage transformers, and JJG 314-2010 Instrument VoltageTransformers



MODEL AND MEANING

Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer
NORMAL USAGE CONDITIONS
  1. Altitude: should not exceed 1000m
  2. Ambient temperature: -5ºC ~ +40ºC
  3. Air relative site: Indoor.

TECHNICAL PARAMETERS
  1. Compliance Standards: GB/T 20840.1&3 and IEC61869-1&2
  2. Insulation level:12/42/75kV, 7.2/30/60kV
  3. Power factor:cosφ=0.8(lag)
  4. Rated frequency:50Hz or 60Hz
  5. Weight: 21.5kg, 30kg
 
Table 1: Transformation Ratio for JDZ10-10(6)A
 
Rated Voltage Ratio (kV) Accuracy Class Rated Output  (VA) Limit Output (VA)
6/0.1/0.1 0.2/0.2 15/15 300
6/0.1/0.22 0.2/3 15/300 300
10/0.1/0.1 0.2/0.2 15/15 300
10/0.1/0.22 0.2/3 15/300 300
 

Table 2: Transformation Ratio for JDZ10-10(6)B
 
Rated Voltage Ratio (kV) Accuracy Class Rated Output  (VA) Limit Output (VA)
6/0.1/0.1 0.2/0.2 20/20 500
6/0.1/0.22 0.2/3 20/500 500
10/0.1/0.1 0.2/0.2 30/30 500
10/0.1/0.22 0.2/3 30/500 500

OUTLINE AND INSTALLATION DIMENSION

Fig 1: Diagram for JDZ10-10(6)A
Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer

Fig 2: Diagram for JDZ10-10(6)B
Jdz10 -10 Indoor / Single-Phase Epoxy-Resin Type Voltage Transformer

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
302
Year of Establishment
1996-09-15