High Voltage Air Sf6 Pole-Mounted Electrical Electric Vacuum Interrupter Circuit Breaker

Breaking Capacity: High Voltage Circuit Breakers
Operation: Manual Type
Arc-extinguishing Medium: Vacuum
Installation: Fixed
Type: Circuit Breaker
Function: Conventional Circuit Breaker, Overcurrent Protection
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
ZW-J
Rated Frequency
50Hz
Rated Voltage
12kv
Rated Current
630A
Mechanical Life
10000times
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year

Product Description

Photos of Product
High Voltage Air Sf6 Pole-Mounted Electrical Electric Vacuum Interrupter Circuit BreakerHigh Voltage Air Sf6 Pole-Mounted Electrical Electric Vacuum Interrupter Circuit BreakerHigh Voltage Air Sf6 Pole-Mounted Electrical Electric Vacuum Interrupter Circuit BreakerHigh Voltage Air Sf6 Pole-Mounted Electrical Electric Vacuum Interrupter Circuit Breaker
General

The new problem of the distribution network is as shown below:
1. When the main trunk circuit is modified, the branch line failure rate is rising;
2. Due to the failure of branch line user and protect mismatch, spread to the whole feeder power outages and lead to liability disputes;
3. Transformer substation grounding selected-line equipment can not satisfy quick find grounding point demand;
4. Due to protective circuits with multilevel add delay, worsening of power network working.
FZW28-12F type excellent solve the problem as above.



Boundaries switch (watch-dog) functions
 
Technical specification
No. Item Unit Data
1 Rated frequency Hz 50
2 Rated voltage kV 12
3 Rated short-time power frequency withstand voltage Interphase, to earth(wet) kV/min 34/1
Interphase, to earth(dry) 42/1
Interrupter fracture, isolated fracture(dry test) 49/1
Auxiliary control circuit to earth 2/1
4 Rated lightning impulse withstand voltage Interphase, to earth kV 75
Arc extinguish chamber Break, Isolation break 85
5 Rated current A 630
6 Rated short-time withstand current and duration kA/s 20/4
7 Rated peak withstand current kA 50
8 Rated short-circuit making current(peak) 50
9 The leak rate of the year   ≤0.5%
10 Main circuit resistance μΩ ≤550
11 Mechanical life Times 10000
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
302
Year of Establishment
1996-09-15