• (H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse
  • (H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse
  • (H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse
  • (H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse
  • (H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse
  • (H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse

(H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse

Breaking Capacity: High
Type: Expulsion Drop-out
Usage: High Voltage
Fusing Speed: FF
Fusing Device: Fuse Holder
Standard: IEC/ANSI/IEEE
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
(H)RW12
Voltage
10-38kv
Transport Package
Export Carton
Trademark
DGG
Origin
China
Production Capacity
500, 000

Product Description

GENERAL

(H) RW12-12 (F) outdoor high voltage AC drop fuse (hereinafter referred to as "fuse") is applicable to the outdoor overhead distribution systems with a rated frequency of 50Hz and rated voltage of 10kV. It is used as a protective element of circuit or electrical equipment in case of overload or short circuit fault of a power system. When traveling normally, the fuse is connected in series in the power line, the fuse is in a tensioned state, and the movable joint is locked. When the line fails, the fault current causes the fuse to blow, the movable joint is released, the fuse tube is quickly dropped, and the circuit is cut off, which plays a role in safety protection for the maintenance of the line and equipment. The load type fuse is added with elastic contact and arc extinguishing cover on the basis of the ordinary type, which is used to open and close the load current in the power system.

The fuse shall comply with technical standards such as GB / T 15166.3 - 2008 high voltage AC fuses - Part 3: injection fuses, DL / T 640 - 1997 outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.



MODEL AND MEANINGS
(H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse

MAIN ADVANTAGES
  1. The insulator is made of high-strength ceramic or imported silicone rubber insulation material, with large creepage distance design, pollution resistance and environmental adaptability, and excellent insulation performance, which meets the requirements of long-distance travel in high sea wave areas.
  2. The upper contact adopts a silver pair design, and the contact stainless steel spring provides contact pressure to ensure good conductive contact, and the contact resistance is very small, no more than 300mW.
  3. The lower contact adopts a silver pair design, which provides a pair of current paths and is not connected with the bare foot of the hinge shaft.
  4. The fuse tube adopts an epoxy phenolic glass cloth tube with fiber lining with a special anti-ultraviolet coating, which has excellent anti-ultraviolet performance.
  5. The parallel groove coupling is made of cast brass. Even if the dimensions are inconsistent, the connection becomes very simple due to the provision of two conduits.
  6. The trunnion is made of high-strength cast bronze and silver plated on the surface. It is pressed on the surface of the hinge to ensure that the closing is aligned with the fuse tube.
  7. The design of the baffle fully meets the rapid separation of the end, the cable strand pops up quickly, and the force transmitted to the fuse can be reduced when closing.
  8. The collar joint ensures reliable tripping after cutting off.
  9. The rated current of the fuse of the same family is large, up to 200A, and the breaking capacity can be strong, up to 16A.
  10. According to the user's requirements, a fixed device for power inspection and grounding can be added to facilitate the user's power inspection and grounding operation.

TECHNICAL PARAMETERS
 
No. Item Unit Parameters
1 Rated Frequency Hz 50
2 Rated Voltage kV 12
3 Rated Current for Fuse of the same family A ≤100 ≤200
4 Rated Breaking Current kA 12.5 16
5 Rated Short-Time Power Frequency Withstand Voltage To Earth (Dry / Wet)
kV/min
42/1
Fracture (Dry / Wet) 48/1
6 Lightning Impulse Withstand Voltage To Earth kV 75
Fracture 5
7 Creepage Distance mm Not less than 372 (e-level)
8 Mechanical Life Times 500
9 Usage Life Years Not less than 20
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.


OUTLINE AND INSTALLATION DIMENSION
(H) RW12-12 (F) Series Outdoor High-Voltage AC Drop-out Fuse

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
302
Year of Establishment
1996-09-15