General
DK6-Y distribution automation station terminal is a new generation of microcomputer station terminal based on Blackfin embedded operating system, DSP digital signal processing technology, and network technology, which integrates telemetry, remote signaling, remote control, fault detection, communication management, and other functions. It is suitable for multi-loop centralized monitoring applications such as switching stations, boundary rooms, power distribution rooms, box transformers, and shutters. Through optical fiber, GPRS, and other channels, it can cooperate with the substation and master station of the distribution automation system to realize automatic functions such as operation status monitoring, fault identification and isolation, and automatic power supply recovery of the distribution line.
Model Number And Meanings
Main Features
☆ Complete three remote (telemetering, remote signaling, remote control) functions;
☆ Metering function;
☆ Plug plate unit module installation structure, flexible configuration;
☆ The main CPU is BF609;
☆ Distributed storage function;
☆ Integrated 10kV cable fault monitoring function;
☆ Integrated reactive compensation function;
☆ Uploading of faults is preferred;
☆ Remote maintenance, monitoring, and upgrading
Environmental Conditions
☆ Sea height: ≤ 1000m
☆ Ambient temperature: Outdoor - 25 ºC~+55 ºC;
The highest annual average temperature is 20 ºC;
The highest daily average temperature is 30 ºC;
Maximum daily temperature difference 25 ºC
☆ Relative humidity: ≤ 90% (25 ºC)
☆ Seismic capacity: Ground horizontal acceleration 0.3g
Ground vertical acceleration 0.15g
Simultaneous action lasts for three sine waves;
Safety factor 1.670
☆ Sunshine intensity (when wind speed is 0.5m/s): 0.1W/cm2 ☆ Maximum wind speed: ≤ 35m/s
☆ Maximum icing thickness: 10mm
Main Advantage
☆ Appearance and structure: 19-inch standard case is adopted, with compact and compact structure design, reasonable layout of internal modules, clear wiring, plug and pull structure, and convenient installation. The running state of the device is indicated by a signal light, which can be monitored outside the device, and has a liquid display screen to monitor the on-site data in real-time, which is convenient for the final printing of on-site commissioning
The character logo is beautiful and coordinated, and the handwriting is firmly attached; The wiring is convenient and reliable, and the identification is accurate and clear.
☆ Input 24 × Two groups, 48 in total, can be used for status detection of high-voltage and low-voltage switches.
Out: 12 × two groups, 24 in total, can be used for the closing and opening control of high-voltage and low-voltage switches or the switching control of capacitors.
Closing medium voltage measuring unit: including two groups of medium voltage measuring unit modules. Each group of unit modules can measure three voltages of one section of medium voltage bus and the three-phase current of three switches [la/lc/o].
That is, it can measure the 3-phase voltage of 2 sections of medium voltage bus and the current of 6 medium voltage switches.
The communication, communication, and remote control function modules are independently configured and support hot plugs and can be easily and flexibly expanded according to needs.
Communication port: 5 S-232/485 ports, 3 Ethernet ports, 1 USB port, 1 GPRS interface
The device has an independent protective grounding terminal, which can be firmly connected to the shell and the ground.
Backup power supply for production and maintenance: the power supply of the test device can receive AC and battery DC power supply at the same time, and can be switched automatically; The device also has a monitoring function for the power supply, and the white dimension nursing can
Set operation indicator light: it has power operation, device abnormal alarm, and other indicators.
It can hold the hot broadcast energy, and the hot plug of the signal board and remote control board will not cause misoperation.
There is a system outage, and the power data can be saved
Indication, the digital signal reset function
Main Technical Parameters
1) Power performance
The device power supply can accept AC and battery DC power supply modes at the same time; Under normal conditions, it is the AC power supply mode. Once the AC power supply is interrupted, the device will automatically switch to the battery DC power supply mode when there is no movement; When the AC power supply is restored, the device will automatically switch back to the AC power supply mode. The device works normally during switching. AC input has a status indicator and remote signaling.
2) The vegetable can realize the status monitoring of the power supply. The power module has an obvious indicator light and can upload the power supply status to the superior system in a letter way; It includes the AC state, whether the battery is under voltage, and the battery maintenance state (battery activation).
3) Input voltage range:
220V 20%AC
40V ~ 55V DC / 20V ~ 28V DC.
4) Battery undervoltage alarm
5) Battery discharge off
6) Output voltage of power module: 40V~55V; 20V ~ 28V
7) Power range of the power module
Communication power supply: 24V, no less than 15W
Operating power 48V, not less than 80W
8) Power supply commercialization test: local and channel dynamic activation, can enter the battery activation function, measure the battery voltage drop, and have an activation indicator light and remote signaling.
9) Complete machine power consumption machine test (excluding battery charging power consumption):
Power supply:<9W
Voltage circuit:<0.5VA
Current circuit:<0.25VA
Power consumption of the whole machine: no more than 30W (DC power consumption).
Terminal output performance indication
-Digital input/output unit indication
Input: passive dry contact input: resolution: 2ms
Control output: relay contact output: 250V, 5A
Contactless level output: 5V, 300mA
Digital input circuit voltage: DC 24V
Isolation: 500V DC photoelectric isolation
Logic status: closed corresponding binary code "1" and disconnected corresponding binary code "0".
Time range of remote signaling anti-shake (anti-shake ability): 10ms~100ms adjustable.
Resolution of a sequence of events (SOE): 10ms
Digital output mode: relay normally opens node.
The remote control node shall be able to preset and cancel.
Any point and any number of remote signals can be merged into one point and uploaded to the master station.
Under abnormal operating conditions such as power on, reset, and power off, the remote control node of DTU shall not have any malfunction.
Output closing time range: 100ms~60s, step length: 50ms, accuracy:+20ms.
Indication of the analog quantity acquisition unit
Voltage: input range: (0~277) V (relative voltage: relative zero line)
Accuracy: Grade 0.3 (0.3%)
Current: input range: (0~5) A
Accuracy: Grade 0.3 (0.3%)
Active power: maximum power: 30MW
Accuracy: Grade 0.5
Reactive power: maximum: 30Mvar
Accuracy: Grade 0.5
Fault current setting range, (6~50) A, must reach level 3 (3%)
Setting range of fault delay time, 40ms~60s, resolution 10ms
Outline And Installation Dimension