Yb27 (11kV, 15kV, 20kV, 24kV, and 33kV) Prefabricated Substation

Certification: CCC, ISO9001
Voltage Level: Medium Voltage
Structure: Cabinet
Rated Capacity of Transformer: ≤ 2000kVA
No Load Voltage Regulation: ± 2 X 2.5 %
Protection Level: IP34
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
YB - 12
Noise Level
50dB
Transport Package
Nude
Trademark
DGG
Origin
China
HS Code
853720900
Production Capacity
100sets/Year

Product Description

General

YB27-12 / 0.4 prefabricated substation is applicable to 10kV ring network power supply, dual power supply or terminal power supply system, as a power transformation, distribution, metering, compensation, control, and protection device in new residential areas, marginal zones, parks, stations, docks, hotels, construction sites, airports and other places.

This product complies with GB / T17467 high voltage / low voltage prefabricated substation and IEC 601330 high voltage / low voltage prefabricated substation

Model And Meaning
Yb27 (11kV, 15kV, 20kV, 24kV, and 33kV) Prefabricated Substation
Usage Environmental Conditions

1. The ambient air temperature shall not exceed 40 ºC, and the average value measured within 24h shall not exceed 35 ºC. The minimum ambient air temperature shall be - 25 ºC
2. The altitude shall not exceed 1000m
3. The surrounding air is not obviously polluted by dust, smoke, corrosive and/or combustible gas, vapor, or salt mist
4. Relative Humidity
The average value of relative humidity measured within 24h shall not exceed 95%, the average value of water vapor pressure measured within 24h shall not exceed 2.2kpa, the average value of monthly relative temperature shall not exceed 90%, and the average value of monthly water vapor pressure shall not exceed 1.8kpa
5. When the equipment is installed, the inclination with the vertical plane shall not exceed 3 °
6. The equipment shall be installed in a place free from violent vibration and impact.
Note: if users have special requirements, they can negotiate with our company.

 

Technical Parameters

No Item Unit Parameters
1 Rated Voltage High Voltage Side kV 12
Low Voltage Side 0.4
2 Rated Capacity of Transformer kVA ≤ 2000
3 No Load Voltage Regulation   ± 2 x 2.5 %
4 Rated Insulation Level Lightning Impulse Withstand Voltage (Fully glass, Peak Value) kV 75
Power Frequency Withstand Voltage 35
5 Low Voltage Side Power Frequency Withstand Voltage
Phase to Phase and Phase to Ground (1min)
Main Circuit 2.5
Control and Measuring Circuit 2.0
6 Noise Level dB 50
7 Cooling Mode Natural Cooling
8 Protection Level IP34

Outline Dimension
Yb27 (11kV, 15kV, 20kV, 24kV, and 33kV) Prefabricated Substation
 
Capacity(kVA) A B C Weight(kg)
100 2000 1720 1660 1560
125 2000 1720 1660 1640
160 2000 1720 1660 1720
200 2000 1720 1700 1830
250 2000 1720 1700 2000
315 2000 1720 1780 2200
400 2000 1720 1780 2480
500 2000 1720 1780 290
630 2000 1720 1980 3490
800 2000 1720 2060 3620
1000 2000 1720 2060 4650
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
302
Year of Establishment
1996-09-15