Certification: | CCC, ISO9001 |
---|---|
Voltage Level: | Medium Voltage |
Structure: | Withdrawable |
Rated Voltage of The Main Circuit: | AC380(400), (660)V |
Rated Frequency: | 50(60)Hz |
Rated Insulation Voltage: | AC660, (1000) |
Customization: |
---|
Suppliers with verified business licenses
Model And Meaning
Usage Environmental Conditions
1. The altitude of the installation site shall not exceed 2000 meters
2. Ambient Temp.: Upper limit +55˚C, The average value measured within 24h shall not exceed 35˚C, and the lowest ambient air temp -15˚C
3. The ambient air temp. shall not exceed 40˚C. And the average value measured within 24h shall not exceed 35 ˚ C. Minimum ambient air temp. -5˚C.
4. The surrounding air is not appreciably polluted by dust, smoke, corrosive and/or flammable gases, vapors, or salt mist.
5. When the equipment is installed, the inclination from the vertical plane should not exceed 5˚C
6. The equipment should be installed in a place free from severe pulling and impact.
Note: if users have special requirements, they can negotiate with our company.
Technical Parameters
Item | Unit | Parameters | |
Rated Voltage of the Main Circuit | V | AC380(400), (660) | |
Rated Voltage of the Auxilliary Circuit | V | AC110, 220(230), 380(400), DC110, 220 | |
Rated Frequency | Hz | 50(60) | |
Rated Insulation Voltage | V | AC660, (1000) | |
Rated Current | Horizontal Wiring | A | 1000, 1250, 1600, 2000, 2500, 3150, 4000 |
Vertical bus (Bus) | 630, 800 | ||
Rated Short-Time Withstand Current | Horizontal Wiring | kA/1s | 30, 50, 80 |
Vertical bus | |||
Rated Withstand Current (Peak Value) | Horizontal Wiring | kA/0.1s | 63, 105, 176 |
Vertical bus | |||
Power Frequency Test Voltage | Main Circuit | V/1min | 2500 |
Auxiliary Circuit | 1800 | ||
Handle | 3750 | ||
Protection Level | IP30, 1P40 |