GENERAL
ZJH-12 series outdoor high-voltage AC floor type metering box (hereinafter referred to as "Floor type Metering box") is applicable to three-phase AC 50Hz and rated voltage 12kV three-phase power system. It can be used for power metering of high-voltage cable incoming users. It can be installed in parks, residential areas, and roadside lawns in industrial and mining areas. It can directly open the door to check the meter low and conduct on-site breaker opening and closing operations.
The floor-type metering box is mainly composed of a vacuum circuit breaker, casting type combined transformer, lightning arrester, live display, and intelligent control device. Its metering methods include a three-phase three-wire system and a three-phase four-wire system. It can be configured with a zero sequences current transformer for grounding protection.
The floor type metering box meets the requirements of GB / T 1984-2014 high voltage AC circuit breaker, DL / T 402-2016 high voltage AC circuit breaker, and DL / T 403-2000 technical conditions for ordering 12kV ~ 40.5kV high voltage vacuum circuit breaker, GB / t17201-2007 and DL / T 721-2013 remote terminal of the distribution automation system.
MODEL DESCRIPTION
USAGE: ENVIRONMENTAL CONDITION
- Altitude: ≤ 1000m, If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly.
- Ambient temperature: -40oC ~ +45oC,
- Maximum daily temperature difference: 25K
- Humidity: Average daily relative humidity: 95%, average monthly relative humidity: 90%.
- Sunshine intensity: not more than 0.1W/cm2
- Wind Speed: 34m/s
- Wind pressure: 700Pa
- Pollution level: e - level
- Icing thickness: Not more than 10mm
- Resistance to floor drain: horizontal acceleration 0.3g, vertical acceleration 0.2g
MAIN ADVANTAGES
☆ small floor area, low investment, and high-cost performance;
☆ it has the functions of automatic power transmission, data processing, display, storage, alarm, and automatic power off;
☆Equipped with anti stealing device, it can reduce unnecessary power loss for the power system;
☆It has the function of prepayment to prevent the user from defaulting on electricity charges;
☆The box is of stainless steel floor type structure, with a beautiful appearance and convenient installation.
MAIN TECHNICAL PARAMETERS
Main Technical Parameters of Vacuum Circuit Breaker Body
No. |
Item |
Unit |
Data |
1 |
Rated frequency |
Hz |
50 |
2 |
Rated voltage |
kV |
12 |
3 |
Rated current |
A |
630 / 1250 |
4 |
Rated short-time power frequency withstand voltage |
Interphase, to earth(wet) |
kV/min |
34/1 |
Interphase, to earth(dry) |
42/1 |
Fracture (dry) |
48/1 |
Secondary circuit to earth |
2/1 |
5 |
Rated lightning impulse withstand voltage |
Interphase, to earth |
kV |
75 |
Fracture |
85 |
6 |
Rated short-time withstand current and duration |
kA/s |
20/4 25/4 |
7 |
Rated Short-circuit breaking current(Effective value) |
kA |
20 / 25 |
8 |
Rated short-circuit Making Current (peak) |
50 / 63 |
9 |
Rated Peak-withstand current |
50 / 63 |
10 |
Rated Short-circuit breaking current breaking times |
Times |
30 |
11 |
Rated operating voltage and Rated Voltage for auxiliary(control) circuit |
V |
AC/DC220
DC48, DC24 |
12 |
Mechanical life |
Times |
10000 |
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate. |
Main Technical Parameters High-Voltage Metering Part
Serial No. |
Item |
Unit |
Technical Parameters |
1 |
Rated Frequency |
Hz |
50 |
2 |
Power Factor |
|
0.8 (Lagging) |
3 |
Rated Primary Voltage |
Three-Phase, Three-Wire System |
kV |
10 |
Three-Phase, Four-Wire System |
10/√3 |
4 |
Rated Secondary Voltage |
Three-Phase, Three-Wire System |
0.1/0.22 |
Three-Phase, Four-Wire System |
(0.1/√3) / 0.22 |
5 |
Voltage Transformer Wiring Mode |
Three-Phase, Three-Wire System |
|
V-V |
Three-Phase, Four-Wire System |
|
Y-Y |
6 |
Rated Primary Current |
A |
5 ~ 600 |
7 |
Rated Secondary Current |
5 |
8 |
Voltage Transformer Accuracy Level |
|
0.2/3 |
9 |
Current Transformer Accuracy Level |
|
0.2S |
10 |
Voltage Transformer Rated Output |
VA |
15/200 |
11 |
Voltage Transformer Limited Output |
500 (Level 3) |
12 |
Current Transformer Rated Output |
10 |
13 |
Polarity |
|
Minus Polarity |
14 |
Rated Short-Time Power Frequency Withstand Voltage |
kV/min |
42/1 |
15 |
Rated Lightning-Impulse Withstand Voltage |
kV |
75 |