Customization: | Available |
---|---|
After-sales Service: | Upon Request |
Warranty: | Upon Request |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical Parameters | Index | ||
Input | Network | 3-phase 3-wire, 3-phase 4-wire | |
Voltage | Rated Value | AC 100V, 400V | |
Overload | Consistent: 1.2 times Instantaneous: 2 times/30s |
||
Consumption | < 0.5 VA(each phase) | ||
Impedance | > 500 kΩ | ||
Current | Rated Value | AC 1A or 5A | |
Overload | Consistent: 1.2 times Instantaneous: 2 times/30s |
||
Impedance | < 20 mΩ (each phase) | ||
Frequency | 45 ~ 65Hz | ||
Output | Electric Energy | Output mode | 2-channel open-collector optical coupling pulse output |
Pulse constant | Active 10000imp/kwh Reactive 10000imp/kvarh |
||
Communication | Output mode | RS485 | |
Protocol | MODBUS_RTU | ||
Analog Quantity | Channel quantity | 2 ~ 4 channels | |
Output model | 0 ~ 20mA, 4 ~ 20mA programmable | ||
Load ability | ≤ 300Ω | ||
Switching Value | Channel quantity | 2 ~ 4 channels | |
Output mode | Normally open relay contact output | ||
Contract capability | AC 250V/1A (Resistance load) | ||
Switching value input | 4 - channel passive dry contact input model | ||
Measuring Accuracy | Voltage, Current | class 0.2 | |
Power | class 0.5 | ||
Frequency | ± 0.05 Hz | ||
Power Factor | ± 0.01 PF | ||
Active electric energy | class 0.5 | ||
Reactive electric energy | class 2.0 | ||
Power Supply | Scope | AC/DC 85 ~ 264V 50/60Hz AC220V ± 10% | |
Power consumption | < 5VA | ||
Environment | Temperature | Operation: -10 ~ 50ºC Storage: -25 ~ 70ºC |
|
Humidity | ≤ 85% RH, free of wet and gas corruption |