Application: Metering
Type: Current Transformer
Phase: Single
Operation Condition: Outdoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
LZZBJ
Insulating Medium
Epoxy Resin
Installation
Extension Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Insulation Level
40.5/95/200kv
Rated Secondary Current
5A or 1A
Rated Frequency
50Hz or 60Hz
Altitude
Should Not Exceed 4000m
Air Relative Site
Outdoor/Indoor
Ambient Temperature
-5ºC~+40ºC
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year

Product Description

Photos of Product
36kv Outdoor CT Single High Voltage Phase Epoxy Resin Casting Types of Energy Meter Current Transformers36kv Outdoor CT Single High Voltage Phase Epoxy Resin Casting Types of Energy Meter Current Transformers36kv Outdoor CT Single High Voltage Phase Epoxy Resin Casting Types of Energy Meter Current Transformers36kv Outdoor CT Single High Voltage Phase Epoxy Resin Casting Types of Energy Meter Current Transformers
General


This type of voltage transformer adopts epoxy-resin vacuum casting and fully closed single-phase structure for indoor use, is applicable for power systems of rated frequency 50Hz or 60Hz and rated voltage up to and including 10kV, used for electric energy metering and voltage measurement.
It complies with the standards GB 20840.1-2010 Instrument transformers-Part1:General requirements, GB 20840.3-2013 Instrument transformers-Part3:Additional requirements for inductive for inductive voltage transformers, and JJG314-2010 Instrument Voltage Transformers.


Technical Parameters

1.Insulation level:40.5/95/200kV
2.Power factor:cosφ=0.8(lag)
3.Rated secondary current: 5A or 1A
4.Rated frequency :50Hz or 60Hz
5.Weight: 95kg


Technical Ratio
 
Single parameter ratio        
Rated primary current(A) Accuracy class Rated output(VA) Rated short-time thermal current(kA/s) Rated insulation level(kA)
50 0.2S/0.5/10P10/10P10
0.2S/0.5/10P20/10P20
15/15/30/30
15/15/20/20
3.6 7.2
60 4.32 8.1
75 5.4 13.5
80 5.76 14.4
100 7.2 18
120 8.64 21.6
150 10.8 27
200 14.4 36
250 18 45
300 21.6 54
400 28.8 63
500 36 72
600 43.2 81
800 0.2S/0.5/10P30/10P30 15/15/20/20 57.6 120
1000-1600 72 144
 
Dual-ratio parameter        
Rated primary current(A) Accuracy class Rated output(VA) Rated short-time thermal current(kA/s) Rated insulation level(kA)
50-100 0.2S/0.5/10P10/10P10
0.2S/0.5/10P20/10P20
15/15/30/30
15/15/20/20
7.2 18
60-120 8.64 21.6
75-150 10.8 27
80-160 11.52 28.8
100-200-300 14.4 36
150-300 21.6 54
200-400-600 28.8 72
250-500 36 90
300-600 43.2 108
400-800 57.6 120
500-1000 72 120
600-1200 72 144
800-1600 100 160
 
Three parameters        
Rated primary current(A) Accuracy class Rated output(VA) Rated short-time thermal current(kA/s) Rated insulation level(kA)
50-75-100 0.2S/0.5/10P10/10P10
0.2S/0.5/10P20/10P20
15/15/30/30
15/15/20/20
7.2 18
75-100-150 10.8 27
100-150-200 14.4 36
150-200-300 21.6 54
200-300-400 28.8 72
300-400-500 36 90
200-400-600 43.2 108
400-600-800 57.6 120
500-600-800 57.6 144
600-800-1000 72 160

Normal Environmental Condition

1.Altitude:should not exceed 4000m
2.Ambient temperature:-5ºC~+40ºC
3.Air relative humidity:≤85%
4.Air relative site:outdoors


Outline And Installation Dimension

36kv Outdoor CT Single High Voltage Phase Epoxy Resin Casting Types of Energy Meter Current Transformers

Order Notice

1. Please specify the model and current e.g. LZZBJ18-35 100/5
2. Please specify the accuracy class and rated output; e.g. 0.2S/0.5/10P20/10P20 15/15/20/20VA
3. Please contact us if there is any specific requirement.
4. Please specify the order quantity and delivery time

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
302
Year of Establishment
1996-09-15