Certification: | CCC, ISO9001 |
---|---|
Shell Material: | Aluminum Alloy |
Voltage Level: | Medium Voltage |
Installation: | Fixed |
Structure: | Floorstanding |
Current: | AC |
Customization: |
---|
Suppliers with verified business licenses
NORMAL SERVICE CONDITIONS
1. The altitude shall not exceed 1000 meters, and the altitude under special use conditions shall not exceed 2000 meters
2. Ambient Temp: Upper limit +40˚C, The average value measured within 24h shall not exceed 35˚C, and the lowest ambient air temp -15˚C
3. Relative humidity:
The Ave. value of relative humidity measured within 24h shall not exceed 95%
The average value of water vapor pressure measured within 24h shall not exceed 2.2kpa
The average monthly relative temperature shall not exceed 90%
The average monthly water vapor pressure shall not exceed 1.8kpa
4. The surrounding air is not appreciably polluted by dust, smoke, corrosive and/or flammable gases, vapors, or salt mist.
5. When the equipment is installed, the inclination from the vertical plane should not exceed 5˚C.
6. The equipment should be installed in a place free from severe pulling and impact.
7. Note: Users can negotiate with our company for special requirements.
No. | Item | Unit | Parameters | |
1 | Rated voltage | kV | 7.2 / 12 | |
2 | Rated Current of Main Bus | A | 630 | |
3 | Rated Current | Incoming Cabinet | A | 630 |
Outgoing Cabinet (Combined Electrical Cabinet) |
A | 125 (Biggest) | ||
4 | Rated Short-Time Withstand Current | kA | 20 | |
5 | Rated Peak Withstand Current | kA | 31.5 | |
6 | Rated Short-Time Making Current (Peak Value) | kA | 50 | |
7 | Rated Active Load Breaking Current | A | 630 | |
8 | Rated Closed-Loop Breaking Current | A | 630 | |
9 | Rated Cable Charging Current | A | 10 | |
10 | Rated Short-Time Withstand Current of Earthing Switch | kA | 20 | |
11 | Rated Peak Withstand Current of Earthing Switch | kA | 50 | |
12 | Rated Short-Time Making Current Making Peak Value of Earthing Switch. | kA | 50 | |
13 | Rated Breaking Current of Cable Point | A | 3150 | |
14 | 1min Power Frequency Withstand Voltage | Phase-Phase Vacuum Fracture | kV | 42 |
Isolation Fracture | 48 | |||
15 | Lightning Impulse Withstand Voltage | Phase-Phase Vacuum Fracture | kV | 75 |
Isolation Fracture | 85 | |||
16 | Mechanical Life Span | Vacuum Load Switch | Times | 10000 |
Isolation knife Earth Knife | 2000 | |||
17 | Load Switch | Average Closing Speed | m/s | 0.6±0.2 |
Average Opening Speed | 1.1±0.2 | |||
3-Phase Asynchrony | ≤2 | |||
18 | Fuse for the Combined Appliance | Maximum Rated Current | A | 125 |
Rated Short-Circuit Breaking Current | kA | 31.5 | ||
19 | Protection Level | IP3X |